MZXRemote Software MZX REMOTE is a Windows based software tool for remote service and support and MZX detection panels. The software provides a full function fire panel repeater running on a PC either locally or over dial up telephone lines. Tyco Fire Products; Section 14: Preaction Systems Single Interlock: Model DV-5 Preaction System with DV-5 Deluge Valve Single Interlock, Supervised - Wet Pilot.
FIM801 Field Interface Module (one MX loop driver)
Tyco Safety Products Driver Safety
The Field Interface Module FIM is the main interface for field wiring on MX detection panels and contains plug-in field wiring terminals, inter board connectors, EMC protectors and filters and general I/O electronics. The FIM801 provides 1 x MX DIGITAL loop and the FIM802 provides 2 x MX DIGITAL loops. Each MX DIGITAL loop can support several kilometers of loop wiring using a mixed topology using multiple loops and spurs.
The FIM provides up to 495mA of loop power to each loop to drive loop powered sounders and other loop power devices. An optional plug-in additional loop cards (XLM800-MX) provide up to 8 x MX Digital loops.
The FIM incorporates the following local I/O connections:
Software House, part of Tyco Security Products, provides reliable security management systems available only through a rigorously trained network of certified integrators. Tyco Security Products and it's portfolio of brands form one of the largest security portfolios in the world. Engineers specializing in Video Security, Access Control, Location Based Security and Intrusion Security provide Tyco Security Products a competitive advantage when it comes to system integration. Tyco Security Products is a leading provider of access control and fully integrated security management systems. The solutions range from reliable, easy-to-install access control for small and medium enterprises to scalable and highly integrated applications for global enterprises.
- 2 x volt free outputs (Default alarm and fault)
- 1 emergency alarm input
- Full monitoring of PSB800 power supply
Tyco Safety Products Driver Training
The FIM incorporates a local I/O bus which allows the local I/O connections to be increased by 24. A variety of I/O expansion boards are available including:
- IOB800 (8 in/8 out) expansion board
The FIM includes two connections to the RBUS one for the local user interface and one for connecting up to 15 remote addresses in the form of up to 2 x operator control modules (OCM800) or up to 15 multi-purpose modules (MPM800).
The FIM provides 3 configurable external serial ports:
Tyco Safety Products Driver Updater
- Port 1 Local printer
- Port 2 Configuration PC or remote diagnostics and upload/download modem
- Port 3 FSI open protocol or Network card/geteway (TLI-800 or MX-FIL)